London Fire Brigade Evidence - Wednesday 24th November 2021 (2/2)

24 November 2021 · London Fire Brigade Witnesses, Counsel to the Inquiry · 2:27:34
▶ Watch on YouTube Open in interactive viewer

Evidence session examining the London Fire Brigade's response to the Grenfell Tower fire, including operational decisions, command structure, and lessons learned.

Key moments

Full transcript

# Transcribed with OpenAI Whisper (medium model)

# Source: Local audio transcription (no YouTube captions available)

00:00:30 Yes, would you ask Ms Cotton to come back in please?

00:00:32 All right, Ms Cotton, ready to carry on?

00:00:45 Yes, sir.

00:00:45 Thank you very much.

00:00:46 Yes, sir.

00:00:47 Thank you, Mr Chairman. Ms Cotton, can we go back to the DCP that we were looking at before the

00:00:52 lunch break? In relation to your specific concern that the DCP may be inaccessible for individuals

00:00:57 with learning difficulties, we heard from Dr. Keween Hatton that she was unaware of any empirical

00:01:02 basis for your concern and that her understanding was that you had shown the DCP to a colleague who

00:01:07 at first look found it confusing. Is that correct? Not in its entirety. So obviously with any new

00:01:16 policy, it was important to ensure if we were to deliver training to our operational crews that if

00:01:23 there was going to be any difficulty in people understanding or in different learning styles,

00:01:30 that we would be able to find a way to adapt that training to sort of cater for that. When I had

00:01:36 first seen the DCP, I had had a conversation with a number of professional colleagues who I was aware

00:01:44 were suffering from dyslexia and a number of those, so about five or six of them, had said

00:01:52 on first viewing it, they found it complicated to understand because it was not sort of as it were

00:01:59 in the line and it was a different approach. So it was just my concern that if we were to introduce

00:02:05 it and to deliver that training, that we would have to make sure that there would be the ability

00:02:10 to adapt it so that we could ensure that all of the operational colleagues could fully understand

00:02:16 it. Right. Was that not so with many, if not all, policies published by the LFB? Every policy would

00:02:24 undergo an equality impact assessment. It would depend on the nature of the content of that policy.

00:02:30 Some people obviously have different learning styles according to different things, some people

00:02:34 it's diagrams, or some people it's writing, for some people it's methods of communication. So it

00:02:38 was ensuring that all of those were covered. Right. But that wasn't of itself, was it, an obstruction

00:02:44 to proceeding with the DCP as a policy? No, not at all. No. We also heard that Dr. Cohen-Hatton had

00:02:49 discussed that issue with Professor Honey, with whom she'd carried out the research. You referred

00:02:54 to his work and indeed himself in your evidence before lunch. And she told us that he, Professor

00:03:01 Honey, had consulted specialists in neurodiversity and dyslexia at Cardiff University. And she told

00:03:08 us that her understanding of their view, with which she agreed, was that the DCM would actually

00:03:13 be beneficial for those with dyslexia rather than inhibitory, because it provided scaffolding,

00:03:21 is the word she used, to support decision making. Were you aware of that view at the time?

00:03:27 No, I believe that wasn't until 2017 that she had that information. So I believe she shared that with

00:03:35 the then Director of Safety and Assurance, Steve Apter. Steve Apter. Were you not involved with

00:03:39 that discussion by that stage, presumably because you were Commissioner? No, I wasn't.

00:03:43 I see. Did you hear about that view at the time? I believe not whether it was that time or some

00:03:50 time later. Mr. Apter did share that with me. You also refer, I think, to a concern that the

00:03:56 DCP had not been tested on level three and four incident commanders. Is that right?

00:04:01 Yes, that's correct. Right. Dr. Cohen-Hatton told us that that concern had never in fact been

00:04:05 directly discussed with her. Is that right? No. Quite early on, when I had a conversation

00:04:12 about her research, she said that the team that had done the research were hoping to get further

00:04:17 funding from CFOA to carry out that research on level three and four incident commanders,

00:04:23 but it was funding dependent. Funding dependent. I mean, her view was that it wasn't a good reason

00:04:28 for rejecting the DCP, because level three incidents are very like levels one and two incidents,

00:04:33 and the results are broadly extrapolatable, they're generalisable. Level four more strategic,

00:04:40 and the elements were covered in any case, as she told us. Would you agree with that?

00:04:43 No, I think that level three and four are fundamentally quite different to level one and

00:04:47 two, and because she had expressed to me that the work was going to be carried out, we were very

00:04:52 interested in seeing the results of that work on more senior officers. Did you discuss with anybody

00:04:59 the fact that the DCP had not been tested on level three and four commanders as a reason for

00:05:05 rejecting the DCP? That was discussed with a number of other factors, with the corporate

00:05:11 management board, with a range of the other things we talked about earlier, as considerations as to

00:05:18 whether or not to adopt the DCP in its entirety at that moment. Right, did you think to discuss

00:05:24 that with Dr. Cairn Houghton herself? Yes, I had discussed that with her. You did, you say you did?

00:05:28 Yes, absolutely. And you also say that there was concern around the extent to which the DCP had

00:05:33 been tested in operational situations. What did you mean by that? So as I understood it from the

00:05:39 way Dr. Cairn Houghton explained it, they had undertaken a number of studies of operational crews

00:05:46 by fitting with body cams and then afterwards interviewing them to discuss the way they had

00:05:52 reached decisions. And then in a simulated environment, a number of officers were

00:05:59 tested using the DMM and the DCP. Dr. Cairn Houghton then explained that what was going to happen next

00:06:05 was once it had been embedded that they would do a further piece of work to look at how well

00:06:11 that was embedded in the operational arena going forward as a method of evaluation and we'd be

00:06:16 very interested in seeing that outcome. Were you aware of Dr. Cairn Houghton's research,

00:06:22 which consisted of precisely that? I think you've just explained it to us, namely the

00:06:30 testing and analysing of decision making at operational incidents. Yes, and that was all

00:06:37 as I understood it when she explained it to me. The actual testing was in a simulated environment

00:06:41 rather than at operational incidents, although they'd gathered information prior at operational

00:06:45 incidents, the actual process while they tested it, because they needed to be able to repeat the

00:06:50 same scenarios and therefore you could only do that at a simulated event, albeit realistic in

00:06:56 real venues, not just by computer simulation. Right, I mean in your statement you're expressing

00:07:03 concern or you're reflecting concern about the extent to which DCP had been tested in

00:07:07 operational scenarios. My question is were you aware of the conclusion of her research,

00:07:13 namely that incident commanders were more likely to be goal-orientated and have better situational

00:07:18 awareness when the DCP was applied as opposed to when the DMM was used? Yes, I was aware that was

00:07:24 the finding that as a result of the academic research she had done and testing in the simulated

00:07:29 environments. In addition to the reasons referred to at paragraph 34 of your statement, which we've

00:07:35 just looked at, can I ask you about some further possible reasons which have been raised? Can we

00:07:42 go to Graham Ellis's statement please at LFB 00118230?

00:07:58 And if we go to page 7 in that statement, paragraph 34,

00:08:02 he says, I recall discussions that took place regarding the IC NOG and the decision control

00:08:10 elements in particular with AC Cotton, Adrian Bevan, LFB head of health and safety, and GM

00:08:16 Drawbridge, as well as many other LFB officers. We collectively considered the decision controls

00:08:21 as stated in the NOG, being that decision controls are a rapid mental review exercise that asks,

00:08:28 a rapid mental review exercise that asks, why am I doing this? What do I think will happen?

00:08:33 Is the benefit proportionate to the risk? The consensus view during discussions was that LFB

00:08:39 incident commanders were already being trained to complete those rapid mental checks under the

00:08:44 existing DMM. Incident command training had always included critical challenge to decision making,

00:08:50 but also explicitly encouraged incident commanders to constantly check, reconsider, and amend their

00:08:56 plan with due consideration to benefit versus risk. Do you agree first that incident commanders

00:09:02 were already being trained to complete these, as he calls it, rapid mental checks? I think that

00:09:09 DSC Ellis's view is that the incident command training and a number of scenarios, the injects

00:09:17 and the questions that were asked were encouraging and educating incident commanders to do that,

00:09:24 and although that if you look at the DMM in its sort of linear approach, it is in boxes and it

00:09:32 doesn't always look that way. I think that the conversations and the training that took place

00:09:37 supplemented that, but I do agree that during the conversation we had that we discussed the absolute

00:09:45 benefit of the decision controls to enhance that process of critical thinking and incident commanders.

00:09:52 Was the fact that incident commanders were already being trained to complete,

00:09:57 as he calls it, these rapid mental checks a factor in the decision not to implement the DCP?

00:10:03 I think it was one of the consideration factors that CMB discussed as well, that the enhanced

00:10:11 enhancement of the DMM with the decision controls was seen as a way of sort of almost having a hybrid

00:10:19 version of it, which would not be such a fundamental change that would require a huge training impact, yes.

00:10:28 Did you discuss with Dr Cohen-Hatton the view that the existing training and the existing model

00:10:34 already incorporated the necessary elements of the DCP as a reason for it not being adopted?

00:10:41 I don't remember the specific detail. Dr Cohen-Hatton and I had several conversations around

00:10:47 the adoption of the DCP versus the DMM. I can't recall the exact detail of those now.

00:10:54 If that was a factor, as you I think agree that it was, do you agree that it would have been

00:10:59 prudent to do so, given her expertise, and at least then to tease out from her why it was she

00:11:05 thought that the existing training didn't cover what she thought it should cover?

00:11:10 I think at that time that Dr Cohen-Hatton hadn't seen much of London Fire Brigade's existing

00:11:18 training. I don't think she had been in London Fire Brigade very long at that point, so it would

00:11:22 have been difficult for her to have commented on existing instant command training, but we definitely

00:11:27 had a conversation about the benefits the decision controls would bring, which is why she was asked to

00:11:34 present them to Babcock and work closely with them to integrate them into the existing training.

00:11:39 Now we've seen that DAC Lee Drawbridge was of the opinion that the only time the DMM,

00:11:44 the decision-making model, did not work was when it wasn't applied properly. Was that a view you

00:11:50 shared? I think it's more nuanced than that. I think that it's very, I could not point to a time

00:11:58 where I felt that an instant commander was directly criticised for not using the DMM and

00:12:08 therefore not making decisions. We used the DMM at the performance review of command and went

00:12:14 through the steps in it, so it was used not only as a briefing tool, as a decision-making tool,

00:12:20 but as a debriefing tool at the PRCs, and I think at that point you could tease out whether or not

00:12:27 there were aspects that instant commanders had not adhered to. For instance, did an instant commander

00:12:33 gather all available information about the risks they might be facing and then if you perceived

00:12:38 they hadn't that would be the conversation that would happen. Right, you say it's more nuanced,

00:12:43 maybe to see if I can get at it slightly differently. Dr Cone-Hatton addressed this

00:12:48 view, the, if I can call it the Drawbridge view, that the only time the DMM wasn't right was when

00:12:53 it was worked wrongly, and she told us at day 182 pages 81 and 82 that that view was inconsistent

00:13:02 with her academic findings and research and her own operational experience while at the LFB itself,

00:13:09 as she was from February 2015, and indeed her own experience as head of ORT after June 2017.

00:13:16 That's what she told us. Can you comment on that? Would you agree with it? I think at the time when

00:13:22 we had this conversation, so this was in, I believe it was around June 2015 we were talking about this,

00:13:29 Dr Cone-Hatton had not long joined London Fire Brigade and actually at that point had not been

00:13:34 out operationally because when we have new officers come into London from another fire

00:13:39 and rescue service we spend a period of time so they can familiarise themselves with London

00:13:44 policies and procedures and do some shadowing. So I don't think at that point she would have been

00:13:49 commenting on London's operational sort of response because she hadn't been sort of in contact with

00:13:56 that at that moment in time. No, but she had been hadn't she in and after June 2017 when she became

00:14:01 head of ORT. By that stage she had gained enough experience at the LFB and was still of that view.

00:14:08 So can you account for that? Yes, by then she would have had operational experience

00:14:13 with London Fire Brigade. Yes, and therefore given that experience and her academic work which she'd

00:14:18 done in 2015, she was of the view that the drawbridge view was not consistent with her

00:14:25 work and experience and given that she rejected it. What is your view about that? What is your

00:14:37 evidence about that? Well clearly I'm not an academic and I wouldn't seek to challenge Dr

00:14:41 Cone-Hatton's academic review because it was a very thorough review and I don't think after that

00:14:48 time we had further conversations around it so I'm not sure what her views were but I understood

00:14:54 that she did not agree with the drawbridge. Did you ever discuss Dr Cone-Hatton's rejection

00:15:03 of the drawbridge opinion with her at any time? Not in 2017, no. Would have been prudent to do

00:15:11 so would it not? I think by that time in 2017 the conversations that were had around the DCP were

00:15:20 being had with Steve Apter who she was working with so I don't think we had further conversations

00:15:25 around it. Would you accept that properly considered none of the possible reasons that we've examined

00:15:31 both before and after the lunch break justified the decision not to implement the DCP particularly

00:15:37 in the light of the detailed research that Dr Cone-Hatton had carried out both with the problems

00:15:42 of the DMM and the improvements which could result or would result empirically identified

00:15:47 from adoption of the DCP? I think that is more complex picture for London Fire Brigade and I

00:15:53 think that the areas that we discussed before lunch and I identified in the difficulty and the

00:15:59 complexity around bringing such a significant change to London Fire Brigade, instant command

00:16:07 training to training 1700 officers in a quite different and new way, those were difficulties

00:16:16 and those were the reasons why that at that time we discussed adopting the hybrid version of

00:16:22 including the decision controls. It's right isn't it that the brigade was the only fire and rescue

00:16:28 services in the country not to have implemented the DCP as part of the national operational

00:16:33 guidance? That's correct. And that was a point noted wasn't it, you may know this, by the

00:16:38 inspectorate as an area for improvement both in its 2019 and its 2021 reports. I'm not familiar

00:16:44 with the 2021 report but yes definitely the 2019 report. Yes and I'll give the reference

00:16:51 for that, the 2019 is at INQ30A's 14796 page 21, second paragraph from the bottom for those who

00:16:58 want to look at it but you would agree with that. Now you were still commissioner I think just about

00:17:04 at the end of 2019 when the 2019 report was published, did it come as a surprise to you to

00:17:09 learn that the LFB was the only outlier in that regard? No I think I was aware of that. You were

00:17:15 already aware. Can I turn to cladding and external fire spread and I want specifically to look at the

00:17:23 institutional knowledge of the brigade of fires involving rapid external fire spread, cladding,

00:17:31 facades, modern methods of construction and the training on those matters. Now we've already

00:17:37 explored your involvement as AC for operational assurance in distilling the lessons from Lackin

00:17:42 into training, can I pick the timeline up in 2014 and in doing that go please to LFB00084762.

00:17:57 This is an email between Graham Ellis and Rita Dexter on the 11th of March 2014 subject

00:18:04 potential rekindling Wardour Street and then there's the incident number given there. We looked

00:18:11 at this with Rita Dexter and she gave evidence and what he says if you go to page three

00:18:22 is in the email of the 11th of March earlier on that day

00:18:27 if you go please to I'm sorry it starts at the bottom of page two my fault I apologize if you go

00:18:33 to the bottom of page two this is this is where this particular chain starts for for my purposes

00:18:40 he says this not wishing to insult your intelligence if you already knew this but King's

00:18:44 ban quotes unquote referred to in this report is the proprietary name for foil backed insulation

00:18:49 board used in modern construction to improve insulation and meet the requirements of the

00:18:54 to improve insulation and meet building regs it is the same as celotex eco therm extra therm

00:19:00 and a range of other major proprietary insulation slabs it generally looks like this and is used

00:19:06 behind plasterboard below floorboards stroke floor sheets and in roof lining the thickness can vary

00:19:11 from 25 millimeters to 150 millimeters and if you turn the page you can just see there's a

00:19:18 photograph there of a piece of king span insulation and three paragraphs down from that he says this

00:19:26 perhaps we can empower our commanders perhaps we need to empower our commanders with the knowledge

00:19:31 that if they can reasonably justify any cutting away we will support them in any claims for damage

00:19:37 done it all comes back to training and ensuring that cbt's and guidance documents are reinforced

00:19:43 by regular practical demonstrations using modern building materials that does not happen as far as

00:19:49 i'm aware the days when a significant minority of our operational workforce was still skilled

00:19:55 trade persons with working knowledge of building construction have long gone did dac ellis as your

00:20:03 deputy and a direct reporter this time raise these issues with you and this was part of an

00:20:09 ongoing conversation around what we termed highly insulated buildings it had become

00:20:18 increasingly apparent that in order to be not only economically viable but environmentally friendly

00:20:24 more and more buildings were being built with insulation panels in them that not only retained

00:20:31 the heat inside the building so that it was more efficient to heat but prevented you know drafts

00:20:37 etc coming in and this was causing a number of issues for firefighters in the operational arena

00:20:45 highlighted tragically by the fire in athelon stour in warwickshire where four firefighters

00:20:50 lost their lives in a vegetable packing factory that was had a lot of this material and what it

00:21:00 served to not demonstrate any external sign of fire when in fact there was a very extensive

00:21:07 fire burning inside the building and unfortunately the crews had gone into the building not being

00:21:12 aware of the severity of the fire and four of those had lost their lives i'm going to cut you

00:21:17 off there i think you may have finished the answer we're going to look at the november 2007 athelon

00:21:23 fire and its aftermath shortly my question was i think a shorter one did dac graham ellis as

00:21:32 your deputy and direct report raise these issues with you at this time yes he did he did how long

00:21:38 had these issues been on the radar of dac ellis or your operational assurance department by this

00:21:44 time this is march 2014 i would think at least since 2007 since athelon stour right

00:21:51 uh and what about his view that cbt's and guidance needed to be reinforced as he put it by

00:21:58 regular practical demonstrations using modern building materials had he raised that with you

00:22:02 in his discussions with you i'm not sure about that i think he would have discussed training but

00:22:08 i'm not sure exactly what he means by regular practical demonstrations well you don't know what

00:22:15 he means by that is it not is it not obvious from the ordinary words he is using sorry in

00:22:21 the context that i don't know whether he means showing operational firefighters a piece of thermal

00:22:27 installation or whether he means going to a building and demonstrating how it was being used or

00:22:32 whether he means showing that in a fire context so there's a number of ways of practical demonstration

00:22:38 to take place yes i see had he raised that with you no i don't think so so you wouldn't have had

00:22:43 an opportunity to ask him what he meant no no clearly um had you yourself raised this question

00:22:49 about training and demonstrations of one kind or another on building modern building materials

00:22:56 with others in the brigade whether the odcb or the training department or gary reason so i think

00:23:03 this was at the time when we were discussing um the um findings from the athelon stour fire where

00:23:10 this was a component so yes we would have been having the conversation in conjunction with that

00:23:15 yes um let's skip up the chain then to page one where we started and here is a a subsequent email

00:23:23 from dac lister rita dexter 11th of march same day 2014 uh later in the day in fact quite late

00:23:31 at night on that day and if you look at the third paragraph in the email he says this by now

00:23:37 babcock training should have a rig at training venues where they can demonstrate how fire can

00:23:42 spread undetected through voids or shafts and a selection of modern building materials such as

00:23:48 king span which they can show to students to highlight the dangers associated with concealed

00:23:54 fire spread it wouldn't even have to be a full-size rig even a glorified wendy house would do the

00:24:00 trick this will become more critical if we move to reinstate recruit training

00:24:06 did dac l is raise that question with you in other words getting babcock to train

00:24:13 through practical demonstrations on a whether a full-size rig a half-size rig or a glorified

00:24:20 wendy house i don't recall a specific conversation um on that matter right did uh i'm assuming then

00:24:29 neither rita dexter nor gary reason came to you with this this didn't filter down to you

00:24:34 no i think this um became um a subject of conversation at odcb

00:24:42 in the talking about um these building materials um i don't know if the conversation around having a

00:24:50 a rig at the training venues was subject to that conversation

00:24:55 um well we'll look at that shortly i think um before we do let's um let's proceed with the

00:24:59 story later into 2014 and what i think you referred earlier uh as the highly insulated

00:25:06 buildings training package can we go to lfb double zero one two one one two five please

00:25:16 email from gary reason to you dac ellis and adrian bevan

00:25:21 as we can see uh and danny and graham please find attached the final report detailing the lessons

00:25:27 learned from the athelstan on sturt incident warwickshire frs is keen that other brigades

00:25:31 are made aware of the content of the report so i have attached the learning points detailed

00:25:36 in the main report that runs to over 80 pages nb the full report can be accessed on the wfrs

00:25:45 can be accessed on the wfrs website and that's warwickshire fire and rescue service

00:25:52 not surprisingly you will see many parallels without with issues that have emerged from other

00:25:57 incidents such as harrow court shirley towers lacanel at our own sai outcomes from my own review

00:26:05 i think that we are already cited and progressing many of the issues detailed in the report

00:26:09 however you will see from the extracts from the bre global report pages 75 to 77 refers

00:26:17 that there are some themes that may be worthy of inclusion in future impd reports to odcb

00:26:24 let me know what you think and whether you feel we have adequately addressed

00:26:27 all of the key operational related issues detailed in the report

00:26:31 so now to be clear we've just discussed this the the athelstan on stir fire november 2007 was as

00:26:40 you say a fire in a vegetable packing warehouse where there was fire spread beyond the compartment

00:26:46 of origin wasn't there yes and that involves sandwich panels in the sense of insulated panels

00:26:51 designed for refrigeration within the building that's correct now let's look at the extracts

00:26:57 that gary reason attaches to his email to you those are at lfb double zero one two one one two six

00:27:14 and i should just say for everyone's record that the full report which we don't need to see

00:27:19 is at inq 30s 14765 so that that is the main document but here are the extracts and if you

00:27:29 look at the extracts this is the learning points document published or issued by the warwickshire

00:27:36 foreign rescue service and if we go to page three in this document there is a heading fire safety

00:27:43 building construction knowledge the top of the page and it says this post incident

00:27:50 incident investigation highlighted that some of the fire safety features of the warehouse were

00:27:54 incomplete and some of these features influenced fire development there was also a lack of

00:28:00 understanding of modern methods of building construction by many of the operational crews

00:28:04 the learning point is that operational crews should be able to recognize the fire safety features

00:28:10 and wider construction methods used in modern building to identify potential hazards and safety

00:28:15 features and then it goes on with identification of sandwich panels the presence of sandwich panels

00:28:22 in the part of the building affected was not widely recognized at the incident the three types

00:28:27 of construction used in the premises had been clad with the same material of the same color which

00:28:32 made recognition in the dark problematic the national guidance available highlighted the need

00:28:37 to identify the presence of sandwich panels although it did not provide guidance on method

00:28:41 of identification the learning point is that national guidance should clarify a consistent

00:28:47 and practical method for identifying the presence and type of sandwich panels used within buildings

00:28:52 see also national ventilation work unfinished overleaf now these kinds of learning points even

00:28:59 from incidents involving other fire and rescue services were central were they not to the work

00:29:05 of your operational assurance department they were did you or your team give consideration to

00:29:10 the learning point that i've shown you that operational personnel should be able to recognize

00:29:15 fire safety features and other modern construction methods and materials yes we did you did what did

00:29:21 you do as a result of that consideration so as a result of that the operational policy department

00:29:30 um were tasked with producing a training package on fires and highly insulated buildings

00:29:41 which was a training package that was designed to identify to cruise not only that the sandwich

00:29:48 panels as i mentioned earlier could hide the true nature of fire inside a building but that they

00:29:57 that fire might travel between them and equally the information that was referenced previously

00:30:04 in dsc alice's email that it may not be easy to identify that there is still fire trapped within

00:30:11 those panels when he talks about rekindling and cutting away the importance of actually being

00:30:16 able to identify that there could be fire contained within them now you've jumped ahead i think to

00:30:22 where we end up or maybe end up on the way which is a training package just to be clear is that

00:30:28 the training package produced as a result of an article in operational news in december 2015

00:30:35 called highly insulated buildings and rapid fire growth yes that's the one so the nature of that

00:30:40 would have been that after that the email from gary reason that graham ellis as part of the

00:30:47 diet would have presented information around that for consideration of an operational news item

00:30:55 and then a subsequent training package yes but i think you've summarized very well some of the

00:30:59 detailed documents are going to show you but let's take it in stages before i go to that can i just

00:31:05 ask you about the second learning point in the extract i read to you namely that national

00:31:09 guidance should clarify a consistent and practical method for identifying the presence and type of

00:31:14 sandwich panels used within buildings was consideration given as to how the lfb could

00:31:20 provide guidance to its crews on that point and i think the point they're making there is that the

00:31:25 expectation was that the national operational guidance team should produce a piece a document

00:31:33 and a piece of research around that which would then be promulgated to all fire and rescue services

00:31:38 to develop training from so that was addressed at what the cfa way was it that would be yes

00:31:43 now let's look back at the email the covering email again just to pick up the reference in it

00:31:53 lfb double zero one two double one two five where he refers specifically to the extracts from the

00:32:01 bre global report you see he says that and he says that some themes may be worthy of inclusion in

00:32:09 future impd reports to odcb now if we go to the extracts themselves which he attached we will find

00:32:19 those at lfb double zero one two one one two six at page 12 so it's within the learning points

00:32:29 document and there it is bre global report paragraph 17.1 highly insulated buildings

00:32:37 and it says this highly insulated buildings are becoming increasingly popular

00:32:41 as a means of reducing the energy consumption of buildings bre global sustainability experts

00:32:47 are heavily involved in the development and certification of highly insulated buildings

00:32:52 of all sizes ranging from domestic properties through to commercial offices industrial buildings

00:32:57 and warehouses the popularity of these buildings is driven by the sustainability agenda which

00:33:04 currently carries far more interest in the construction industry and is currently achieving

00:33:08 far more rapid development than fire the fire safety agenda as the level of insulation afforded

00:33:15 to buildings increases two factors pertaining to the fire are affected and then he explains what

00:33:21 they are and if you go down then to the next page and the next heading paragraph 17.2 rapid fire

00:33:29 growth he says this or it says this partly as a side effect of the increased insulation afforded

00:33:35 to buildings but also as a result of changing materials present in and around buildings rapid

00:33:40 fire growth is becoming increasingly common during the course of carrying out the reconstructions

00:33:46 it was noted that modern fire and rescue service training involves the use of simulator units these

00:33:52 units often show firefighter trainees fires that burn at a steady rate for a considerable period

00:33:58 of time they do not show a fire growing suddenly from a relatively small well-contained fire

00:34:04 to a fire that is engulfing an entire compartment and extending beyond the boundaries of the

00:34:10 compartment as a result trainees are not necessarily taught how to identify signs and symptoms

00:34:16 of impending sudden fire growth and how to respond to these signs and symptoms

00:34:22 Now Gary Reason told us when he came to give evidence that it was that information

00:34:27 in 17.2 in particular that he considered worthy of inclusion in future IMPD reports to the ODCB

00:34:35 my question for you is did you did you direct your team to pick up that issue and make sure

00:34:40 that it was reflected in the next IMPD report for the ODCB?

00:34:44 Yes that's what I was referring to earlier that that was the report that then came to ODCB where

00:34:49 the conversation was had around highly insulated buildings

00:34:52 so yes is the answer to that question but let's look and see how that plays out

00:34:56 can we please then go to the response to the email that Gary Reason sent from DAC Graham Ellis at

00:35:01 lfb 00088107 if you look at the second email down on that page it's 12th of November 2014

00:35:13 same day and he copies you in as he does Adrian Bevan and he says this sir I think you are right

00:35:21 in saying that many of the identified lessons have been considered and actioned by the LFB

00:35:26 the need for improved and more frequent operational and command training is something that we will

00:35:31 hopefully address further through the ongoing review of IC training they have clearly identified

00:35:36 the need for more frequent and enhanced training as operational exposure of the LFB and the need

00:35:41 for more advanced training as operational exposure of staff decreases a few initial observations are

00:35:47 that we can sit we should consider an ops news article of highly insulated buildings

00:35:52 we are already seeing examples of compartment fires in modern well insulated properties

00:35:57 the challenges associated with firefighting in such premises will no doubt continue to test us

00:36:02 given the unprecedented increase in the development of modern high-rise premises across London

00:36:08 and in the email above that if we can see that together Graham Ellis writes to you and Adrian Bevan

00:36:13 a few days later later in the month 27th of November 2014 as follows we have shortlisted fires

00:36:22 in highly insulated buildings quotes on quotes on the wish list for the next main ops news

00:36:28 and better and more frequent incident command training is being addressed via the review of ICT

00:36:33 I think you were referring to that weren't you in your answer now we will we will come on to look

00:36:39 in a moment at the highly insulated buildings ops news article and its associated training but

00:36:45 before we do that it looks from this email as if this was not a new problem and was already known

00:36:50 to your department would that be fair yes so it was making itself present in a number of different

00:36:57 areas we had experienced a large number of building fires that were

00:37:05 timber frame buildings that were being insulated with these sandwich panels and we'd had a number

00:37:11 of very high profile fires where before the external matter was put the external face was

00:37:18 put in the building they had fires and they burnt very rapidly because there was no protection

00:37:23 afforded to them so we'd seen two or three 20 and 30 pump fires in these buildings under construction

00:37:31 and then a number of other issues with things like sandwich panels in warehouses just pausing there

00:37:38 you say we've had a number of very high profile fires where before the external face was put on

00:37:45 the building had fires and they burned very rapidly what was the material that was burning

00:37:51 in those fires the insulation panels and the wood from the timber frame cladding right

00:37:57 and can you remember a particular type of insulation what whether it was pir pur a brand

00:38:03 no i'm sorry i'm not aware of that

00:38:07 now given that the lfb was seeing examples as it said of fires and these kinds of premises and

00:38:14 the unprecedented increase as the words that are used by graham ellis in the development of

00:38:19 modern high-rise buildings is it right that the lfb had sufficient evidence of a trend

00:38:24 in its corporate knowledge so as to justify it being fed through the lfb's diat process and

00:38:30 through the odcb into training yes that's what graham ellis is referring to here yes i'm just

00:38:36 taking it in stages but that so you agree with what i've put to you yes i do yes now before we

00:38:40 leave this email did you yourself take any additional steps or instruct anybody within your

00:38:45 department to take any additional steps to investigate the lessons

00:38:50 to be learned from the atherstone on the stuart incident so these graham ellis had

00:38:58 as he said looked at the other issues as was asked by gary reason and identified that they

00:39:04 were being addressed in other areas of our training and that the incident command was being

00:39:09 addressed in the incident command review so it was this specific issue that was the area of concern

00:39:14 so was the decision to take the highly insulated buildings ops news article to the odcb deemed

00:39:21 at least by you to be a sufficient response to the problem identified in the bre report on

00:39:28 atherstone yes yes thank you now let's go to the odc b minutes next lb lfb triple zero four zero

00:39:36 six one nine please

00:39:40 this takes us to march 2015 and this is the minute of the board's meeting on the 16th of march 2015

00:39:47 we can see from that you were present i think we've looked at this yesterday because we looked at

00:39:55 parts of it but if you go please down to the attendees we can see that you were there as the

00:40:00 fourth attendee as a coa if you look at item three on the same page for which we will need

00:40:06 to scroll down you'll see impd sixth monthly report july to december the hoop to discuss the

00:40:15 issues relating to highly insulated buildings and rapid fire growth on page two with the hohs

00:40:22 hoop is i think peter cowell isn't it that's correct ahead of operational procedures and hohs

00:40:29 was adrian bevin health and safety yes that's correct yes as we know i think adrian bevin

00:40:34 reported to you he's is yes now we have a copy of the six monthly impd report for that time

00:40:40 march 2015 that is at lfb triple zero eight four three nine five can we please go to that

00:40:52 uh you can see that it's called the operational directorate's coordination board date march 2015

00:40:58 report by dac g ellis and the report title as we can see there is the incident monitoring six

00:41:03 monthly reports can i take it that you would have read that yes at the time uh do you remember

00:41:09 whether this report was discussed at this at the odcb meeting the minutes for which we've just seen

00:41:14 yes it would have been yes if we go to page four of this report

00:41:20 you can see that it says there's a heading um proposed articles for operational news

00:41:25 30 december 2015 and then at the very bottom of the page you can see item two highly insulated

00:41:32 buildings and rapid fire growth and then if we turn the page please to page five at the top of

00:41:36 page five it says this recent reports from across the uk fire sector have highlighted the specific

00:41:42 dangers associated with fighting fires in highly insulated buildings as the level of insulation

00:41:47 afforded in modern buildings increases two factors pertaining to fire are affected the ability of

00:41:53 such buildings to contain heat increases this means that less energy is required to heat a room

00:41:58 to the point where flash ever might occur and the temperatures that can be achieved during a fire

00:42:03 are increased the external indicators that a fire is occurring are reduced highly insulated buildings

00:42:10 need to be well sealed gaps or cracks in the building envelope allow heat to leak out reducing

00:42:15 thermal efficiency and reducing their environmental performance as a result of steps taken to reduce

00:42:21 heat loss and seal gaps less smoke from a fire will be able to exit the building to be seen by

00:42:27 passes by all members of the fire service attending an incident rapid fire growth it continues is

00:42:34 becoming an increasingly common feature in highly insulated buildings studies have shown that

00:42:40 firefighters have often been unprepared for such rapid fire growth and as a result of not used

00:42:45 effective firefighting tactics compartment fire behavior training in simulator units has contributed

00:42:52 towards this lack of preparedness in that the fire in these units rarely extends past the compartment

00:42:58 of origin and therefore firefighters are not necessarily taught how to identify signs and

00:43:04 symptoms of impending sudden fire growth and there's a recommendation which we'll come back to

00:43:12 uh in a moment on the basis of this document thus far do you accept that the lack of preparedness

00:43:19 on the part of firefighters for fires spreading beyond the compartment of origin was a key

00:43:24 concern for your department yes in this respect in that um i think that the fact that the

00:43:31 that method of insulation contained any visible signs of fire um outside meant that fire could

00:43:39 meant that fire could spread inside those buildings um and that firefighters were

00:43:45 not necessarily prepared to be going into a building where there was such a well-developed

00:43:49 fire that could have spent spread beyond the compartment of origin and there had been no

00:43:54 external signs of it yes and indeed the second part of this which is that firefighters were not

00:43:59 necessarily taught how to identify signs and symptoms of impending sudden fire growth so

00:44:04 it's the second aspect of the similar problem yes definitely and i think that they're right that the

00:44:09 simulated units that unfortunately were very popular for fire behavior training

00:44:16 not least of all we had the problem in london because of emissions where you weren't allowed to

00:44:23 do the type of demonstration that used to take place meant that the training was quite restricted

00:44:29 in that manner now it was right wasn't it that according to dac ellis the lfb firefighters were

00:44:38 not properly trained or prepared for what to look for by way of symptoms of impending sudden

00:44:44 fire great perhaps for the reasons you've identified but that was correct wasn't it

00:44:47 yeah they weren't necessarily as prepared as they could be um they had some training but not

00:44:51 to the extent where that we would like them to have had i put it this way is there anything in

00:44:56 the paragraph that first paragraph on that page that you disagree with no there isn't no now when

00:45:01 your department came to realize that that that all of this was the case did it not then immediately

00:45:07 strike you that the lfb's post-laconal training clearly had not as the coroner had recommended

00:45:14 prepared crews in those matters now i don't think that line was drawn because this was talking about

00:45:21 this was as we've talked about result of the astor and stout fire which was a fire in a warehouse

00:45:27 and the conversations we were having here were around sandwich panels and the ability of those to

00:45:34 insulate fire and have no visible fire signs which was a very different set of circumstances

00:45:39 than the fire at lacanel which was obviously a very visible external fire spread and the internal

00:45:46 spread of the fire was due to modification in the building well you'll recall and we if we need to

00:45:54 we can go back to it but the coroner had recommended that crews be prepared or consideration be given

00:45:59 preparing crews to and i'm quoting anticipate that a fire might behave in a manner inconsistent

00:46:04 with the compartmentation principle you'll remember i read that to you yes i'll do the

00:46:08 recommendations looking at the second part of this paragraph starting with the words rapid fire growth

00:46:15 and ending with the words therefore firefighters are not necessarily taught how to identify signs

00:46:21 and symptoms of impending sudden fire growth does that not or did that not strike you at the time

00:46:28 as as revealing the possibility at least that the lfb's post lacanel training had not covered that

00:46:36 issue no because this is actually a different issue so when they're talking about impending

00:46:41 sudden fire growth earlier on in the bre report it talked about the fact that because the rooms

00:46:47 are insulated then it takes far less heat and build up to develop the fire to flash over and

00:46:54 it's looking at that that's what the sudden fire growth is that firefighters need to be able to

00:46:59 identify the signs and symptoms of a flash over which is when a fire is contained and then you

00:47:04 open the door to extinguish the fire and it can then spread out of the compartment which is quite

00:47:10 a different set of circumstances than that which was the training at lacanel the point for well i'm

00:47:15 not sure i understand that let me try this slightly differently if you look at the last four lines

00:47:20 of this report and this is a report in the odcb so it's absolutely right in the in the lfb's

00:47:27 knowledge it says this compartment fire behavior training in simulator units has contributed

00:47:33 towards this lack of preparedness in that the fire in these units rarely extends past the compartment

00:47:38 of origin etc yes did that not tell you that the lfb's post lacanel training had not taken on board

00:47:46 the coroner's recommendation back in 2013 to anticipate that a fire might behave in a manner

00:47:51 inconsistent with the compartmentation principle no because this is specifically talking about

00:47:56 training and simulator units so that as an entity i agree would not give firefighters the ability

00:48:02 to recognize fire spread beyond the compartment of origin because the container is one compartment

00:48:08 are you saying that this was a this was a um focused in a problem related only to simulator

00:48:16 units but there was plenty of other fire behavior training that that demonstrated or taught

00:48:22 firefighters to anticipate that a fire might behave in a manner inconsistent with the

00:48:26 compartmentation principle and so this aspect specific aspect of training did not teach them

00:48:31 that and was a very limited aspect of delivering training i think that we were all struggling in

00:48:37 the uk fire service with real fire training as we called it and the ability to deliver that to

00:48:42 firefighters i think that you know as a number of people have discussed there is no better training

00:48:48 than real life real fire training and there wasn't sufficient of that across the uk fire service for

00:48:55 anybody and i think that the advent of the growing increasing use of insulated material

00:49:03 had led to a problem with our ability to train firefighters to be prepared but

00:49:08 that was not the same aspect about training firefighters to understand fire leading a

00:49:14 compartment of origin by in a normal block that wasn't a highly insulated block it was a

00:49:20 quite a different matter it's quite difficult to explain but it's a quite a different

00:49:24 set of circumstances than that in a highly insulated contained building

00:49:30 i'm struggling i'm afraid that may be my fault let me just try it again one more time slightly

00:49:34 differently um the the last part of this paragraph paragraph about rapid fire growth

00:49:41 says what it says it says and then goes on to say compartment fire behavior training

00:49:45 in simulator units has contributed towards this lack of preparedness are you saying that that was

00:49:50 the only problem and if one ignored the simulator units problem in fact crews were regularly being

00:49:56 fully and satisfactorily trained about behavior of fire beyond the compartment of origin i would

00:50:01 definitely not say fully and satisfactorily i think the adequacy of real fire training was definitely

00:50:08 lacking but the the simulator units were one of the key problems simulator units one of the key

00:50:14 problems and presumably not properly counterbalanced by adequate training on fire spread beyond the

00:50:19 compartment of origin in any other respect not in real fire training no i think it was purely in

00:50:24 theoretical input because of the constraints of the real fire training unit did you do anything

00:50:29 in response to what dac graham ellis was saying here in this part of the report so this report

00:50:35 was to go to odcb where we would have the conversation we had the conversation with all

00:50:39 colleagues um and the decision was taken that the operational policy department who owned

00:50:46 all the firefighting policy and tactics would develop a training package right did you take

00:50:52 any steps to liaise with the training department or babcock in that respect no this was a dac

00:50:57 ac peter cowops department that was the commissioning department for this training

00:51:02 why because it was a firefighting policy which were all owned by operational policy under peter cowop

00:51:09 was it not also an incident ground policy which fell under your no no no it all sat within peter

00:51:17 cowop's world right but nonetheless it's your report ellis who's bringing this essentially

00:51:24 through you to the odcb no yes and the reason for that is that as part of the operational assurance

00:51:30 horizon scanning we would bring recommendations as we discussed from other fire and rescue services

00:51:36 which would then feed in as part of the diop process the result of which would be

00:51:41 ops news reports and developments of training packages by the relevant department who owned them

00:51:47 right do you know whether what is said here by graham ellis was then raised as a matter of

00:51:52 significant concern and earmarked as something to be addressed in training as a matter of urgency

00:51:57 so this was then at the odcb taken on by peter cowop as operational policy to develop that

00:52:05 and i know that graham ellis had a number of conversations with peter cowop when he was

00:52:12 developing this training package right did you ever have cause given what graham ellis is saying

00:52:17 here to consider whether crews needed to revisit the training that they had had in response to

00:52:22 lacanel notwithstanding that they had already had some training no because this was a different

00:52:29 issue around the insulation material and the obviously the the risk to the firefighters from

00:52:36 going into a fire compartment where they couldn't see that there was a fully developed fire inside

00:52:40 right and you say it was a different issue i think i'm challenging you on that perhaps too

00:52:48 gently and it wasn't a different issue was it was the same issue because it's all to do with

00:52:51 training firefighters about what to do and what to look for in circumstances where there is a risk

00:52:56 that the fire will spread beyond the compartment of origin and that was a lacanel point so i agree

00:53:01 with you it's about training firefighters but the the the issue that is being discussed here was

00:53:07 around the fact that the insulation of these buildings meant that the fire could develop

00:53:12 inside a building without any external sign whereas obviously at lacanel it was very obvious

00:53:17 that the fire was developing the building and spreading so yes the aspect of training

00:53:22 firefighters to recognize fire could extend beyond the compartment of origin but this was

00:53:27 specifically around the fact that fires would develop and be undetected and that firefighters

00:53:32 could be at risk or lose their life as they tragically did at athelon stowell by entering

00:53:38 a building where they were unaware that a rapidly developing fire was in progress

00:53:44 so your so i've got your evidence on this you're saying that this issue was really nothing to do

00:53:49 with lacanel because this was all about unseen fire spread because of the circumstances in which

00:53:53 the compartment came to be insulated that was the origin of this from athelon stowell yes

00:53:58 whereas in fact lacanel was also about unseen fire spread through voids so what's the difference

00:54:04 so lacanel very obvious ex uh fire spread they could see that the building from the moment their

00:54:09 ride was on fire because it was very visible so they knew that the fire was inside the building

00:54:14 um fires like athelon stowell the crews turned up and were unaware that there was a fire present

00:54:19 in the building that was the difference yes fire spread um through compartments is something

00:54:25 firefighters need to be trained on but the i'm saying that the origin of this piece of training

00:54:29 was due to fires that were not visible from outside

00:54:36 let's go to the uh report again at page five which is now the recommendation put forward by dac ellis

00:54:45 uh underneath the passage i've been asking you about and he says odcb is requested to consider

00:54:49 an obs news article on highly insulated buildings and the dangers of rapid fire spread

00:54:55 odcb is further requested to consider a proposal for a training solution to address the issues

00:55:01 highlighted the training intervention should give firefighters an awareness of the increase

00:55:07 in the number of highly insulated buildings under construction in london and provide examples of

00:55:12 the construction techniques and materials used the training solution should also highlight the

00:55:17 dangers associated with firefighting in such buildings and outline how to identify signs and

00:55:23 symptoms of rapid fire growth and firefighting tactics that should be should be deployed to

00:55:28 contain and extinguish such fires now uh that that's uh to put it very bluntly um entirely

00:55:39 applicable to what happened at grenfell isn't it um i feel i may be not explaining myself very well

00:55:48 the aspect of training firefighters to identify signs and symptoms of rapid fire growth and

00:55:54 firefighting tactics absolutely but the issue here is about understanding the fact that

00:56:00 firefighters could enter a building that was highly insulated and they would have no awareness

00:56:06 that the fire was taking place inside and therefore they could be at risk from entering a compartment

00:56:12 where a sudden rapid fire growth occurred by the introduction of oxygen by them opening the door

00:56:17 into that compartment and they could be subject of a flash over which would then mean that

00:56:21 compartment would become compromised and the fire would spread beyond that compartment

00:56:26 so that's also a vital piece of training to keep firefighters safe yes that i understand like what

00:56:31 i'm really suggesting to you is that you've become rather enmeshed in the original specific

00:56:36 context but not actually looking at the breadth of the recommendation that came out of it it's

00:56:41 right isn't it that the recommendation that came out of it wasn't limited to making firefighters

00:56:47 alert to the possibility that there was unseen fire spread within the compartment it went much

00:56:51 more widely didn't it as we can see yes so it's why it is about the um the fact that lots more

00:56:58 buildings are being built with highly insulated material and that can cause rapid fire spread it's

00:57:03 a wide ranging area but the the risks associated at that time were to do with the risk to firefighters

00:57:10 following the death of four of our colleagues can i just um see if we can clarify this a little bit

00:57:16 listening to your answers i have the impression that your understanding of the fire at

00:57:23 Athelston was that it the building contained a number of compartments created by the use of

00:57:31 insulated boards and therefore the individual compartments within the building could contain

00:57:41 a fire whose presence was not apparent until perhaps you opened the door and went in and then

00:57:48 the introduction of oxygen could create a very rapid well flash over perhaps is it is that your

00:57:55 understanding of the situation that occurred there yes whereas it might be said that the problem at

00:58:03 Grenfell was not the existence of an undetected fire but the occurrence of fire in the external

00:58:14 envelope of the building because the materials would support a very rapidly developing fire

00:58:21 visible as it was on the outside yes that's correct sir yeah right thank you but in light

00:58:27 of that distinction that the chairman has helped you draw would you accept that the recommendation

00:58:33 here which we can see on the screen covered both of those eventualities yes it covered the

00:58:39 fact the firefighters needs to be trained to be aware of those issues yes yes thank you

00:58:43 now peter groves told us that the development of an operational news article and a training package

00:58:48 was a sign of a topic's importance do you agree with that yes yes and do you recall whether the

00:58:53 importance of this topic was actually discussed at this odcb meeting yes it would have been right

00:58:59 do you remember what was said um no i imagine we would have had a conversation around the fact that

00:59:06 this had generated the result of loss of life of four firefighters and the significance of that

00:59:11 information and how important it was to ensure that our crews were trained to recognise the

00:59:19 signs and symptoms of that yes then let's then turn to the minutes of the next odcb meeting which

00:59:25 happened in june 2015 that's at lfb three zeros four zero six four seven

00:59:35 there it is on the screen 15th of june 2015 we can see uh that you were not there

00:59:41 because your name is absent from the list of attendees peter cowp is there adrienne bevan is

00:59:47 also there as head of health and safety for ac danny cotton yes yes so did you depute him to turn

00:59:54 up at this meeting on your behalf um adrienne bevan was a standing member of the odcb but he would

01:00:00 have attended this uh nominally for me as well as i my apologies are shown yeah did you provide him

01:00:05 either with notes or some kind of oral update to prepare him for that meeting uh no because he

01:00:11 would have been at previous meetings to understand uh and he would have seen the meeting minutes

01:00:15 right did he feed back details of this meeting to you afterwards he would have done yes right you

01:00:21 say he would have done because that was his habitual practice and you have no reason to think he would

01:00:24 have departed from it indeed yes um can we look at item four please at the very foot of page one

01:00:31 uh it says there agreement of operational news themes the hoop that's peter cowp

01:00:39 reported that after discussion with oa which i think must have been adrienne bevan for present

01:00:43 purposes an article was to be prepared and issued regarding ventilation issues and materials of

01:00:48 construction this was considered relevant rather than specifically subjecting the issues relating

01:00:54 to highly insulated buildings and rapid fire growth agreed to come to a decision to remove

01:00:59 and rapid fire growth agreed to continue with existing themes now is it right that you and

01:01:04 peter cowp uh who was the head of operational procedures had decided uh that the article

01:01:11 should focus on ventilation and materials of construction rather than on rapid fire spread

01:01:17 no i didn't have a conversation with peter cowp about that did uh right let me try differently

01:01:22 did the hoop and someone in oa have that discussion um i recall graham ellis speaking to

01:01:29 peter cowp and being very insistent um that the um article and the training should cover

01:01:38 the matter as we had discussed it originally um and that it should cover all aspects uh of

01:01:44 the recommendation that dac ellis had made uh does that tell us that

01:01:52 well what was the up what was the upshot of that discussion um so graham ellis pressed the point

01:01:57 with uh peter cowp that that was his belief that that was what the um article was to cover um

01:02:03 peter cowp as the head of operational assurance and therefore the owner of the policy and therefore

01:02:09 the new news article and the subsequent training um was fully aware of graham's views on it

01:02:17 and then he was the one who was responsible with his team for taking that forward do you know why

01:02:22 as it appears from this minute at least peter cup decided on that narrower focus for the

01:02:26 operational news article rather than on rapid fire spread symptoms of impending sudden fire

01:02:33 growth or firefighters not being prepared for fire spread beyond the compartment of origin

01:02:37 no i'm not i don't know why i know that graham ellis had a detailed conversation with him about

01:02:42 it did that mean that the article as then proposed hereafter didn't actually address the concern

01:02:48 raised in the impd report namely that firefighters were not adequately prepared for fires which

01:02:53 spread rapidly beyond the compartment of origin um have you got the specific um article that was

01:02:59 in the ops news to refresh my memory please yes do you want to see that yes please thank you

01:03:04 before i go to that are you able to answer my question without it no sorry you're not

01:03:11 it's lfb triple zero six one four eight two

01:03:16 this is 30th of january 2016

01:03:22 and there's the front page and you can see the date in the top right hand corner

01:03:27 uh if we go please to page five you can see what what is said fires in highly insulated buildings

01:03:35 now there's quite a lot of this i want to show you not least because i think it will help you

01:03:39 answer my question so bear with me um modern methods of construction have developed significantly

01:03:44 over recent decades to improve the energy efficiency of buildings developments in building

01:03:50 construction insulating materials and building techniques have led to increasingly well sealed

01:03:55 buildings and compartments such advances have influenced fire behavior in a number of significant

01:03:59 ways developments in fire resistant material and prevention measures have reduced the number of

01:04:05 fires attended by fire and rescue services however modern methods of construction and

01:04:10 extensive use of compartment insulation can now have a significant impact on fire behavior

01:04:15 specifically and in the first bullet point the ability of highly insulated buildings to contain

01:04:21 a rise in temperature this means that less energy is required to heat a room to the point where

01:04:25 flash over might occur and the temperatures that can be achieved during a compartment fire

01:04:31 are higher when compared with traditionally built buildings the external indicators of the fire may

01:04:36 be reduced highly insulated buildings are well sealed and as a consequence less smoke and fire

01:04:41 will be visible to passers-by or members of the fire service arriving at an incident crews need

01:04:46 to be aware that it is not just new builds that contain modern construction and insulation

01:04:51 technology when older building are refurbished they are often retrospectively fitted with

01:04:56 insulation and compartments will be sealed to increase energy efficiency identifying the exact

01:05:01 nature of construction and internal technologies from the exterior of a building remains a difficult

01:05:06 task for crews at operational incidents and then there's an example given of a march 2015 fire at

01:05:12 a travel lodge hotel in east london and picking it up halfway down that column it says mindful of

01:05:20 the nature of construction and the fact that an intense fire had remained contained in the

01:05:25 compartment the incident commander i.c. quickly developed a safe tactical plan with crews

01:05:29 demonstrating excellent firefighting techniques in the way they dealt with the fire crews anticipated

01:05:34 a well-developed and intense compartment fire and ensured that everyone was evacuated from the fire

01:05:38 floor before making a safe compartment entry with an appropriate weight of attack

01:05:43 and then there's some technical report reportage there about what they did national operational

01:05:48 guidance project nag has worked closely with the building research establishment to create a body

01:05:52 of research about building construction building types and firefighting facilities this information

01:05:57 is available on the national operational guidance website and the research is the website for

01:06:03 research is given there so that's the article i've read it to you almost in its entirety

01:06:11 just looking at it would you agree that far from illuminating an over-reliance on

01:06:17 compartmentation and a failure to anticipate rapid fire spread this article instead encourages

01:06:22 and reinforces traditional training on compartmentation firefighting tactics

01:06:26 I think the aspect it does pick up is the recognition of the fact that insulated compartments

01:06:34 can contain an intense fire that if you open the compartment of origin could then result

01:06:40 in that rapid fire growth so when it talks about the example in the travel lodge it quite rightly

01:06:46 suggests that the crews made sure that everyone was safely out of the potential risk area so if

01:06:52 the fire had extended beyond the compartment of origin then it wouldn't put anyone in harm's way

01:06:58 and it also tackled the issue of fires using appropriate a firefight using appropriate

01:07:03 firefighting tactics to deal with that potential rapid spread of fire it does cover that area

01:07:14 it covers that area but it doesn't cover everything does it it doesn't cover

01:07:18 the anticipation of sudden impending rapid fire spread or spread beyond the compartment of origin

01:07:25 i think it does cover the rapid fire spread because that's what's articulating in the

01:07:30 travelodge example but i agree it does not cover the spread beyond the compartment of origin

01:07:36 no it deals with intense compartment fires which are unseen and sudden and surprising perhaps but

01:07:42 not the full breadth of the recommendation no it doesn't know why is that um whether that was

01:07:48 due to be picked up in the training package which will be on the back page um i imagine that that

01:07:53 was going to go into more detail reinforcement of traditional training on compartmentation

01:07:58 firefighting is precisely what the impd report warned against isn't it

01:08:04 um in a way yes yes and yet the middle paragraph there about the travelodge incident

01:08:10 is quite congratulatory isn't it um i think that uh makes reference to the fact that it was um

01:08:17 exactly an example of a fire that was contained within um a building with insulation uh and that

01:08:24 firefighters anticipated uh an intense compartment fire that could spread beyond the compartment of

01:08:30 origin and therefore evacuated everyone from the floor so i think it did recognize those factors

01:08:35 if i was to pick this up as a firefighter what would i learn from the travelodge hotel experience

01:08:40 has reported there other than that the incident commander quickly developed a safe tactical plan

01:08:45 and the crews demonstrated excellent firefighting techniques i think that you would read the fact

01:08:50 that modern methods of construction meant that there were premises that had highly insulated

01:08:55 compartments in them where you might not see or recognize external indicators of fire

01:09:01 and that those buildings were able to contain a rise in temperature and the flash over could occur

01:09:06 and that the crews attending this fire had prevented that flash over and fire spread occurring

01:09:11 by developing a tactical plan to prevent that and to keep the members of the public and everyone

01:09:17 else safe yes well i can see that it might raise awareness of the risks but it doesn't train anybody

01:09:22 on how to deal with them does it the purpose of ops news articles weren't training they were

01:09:27 information pieces the training then came attached as a on the back page as we saw yesterday

01:09:32 you would have had sight of and is this right and approved this article before it was published in

01:09:36 operational news i wouldn't have approved this article no this was approved by um acp to cow up

01:09:42 did anybody to your knowledge ever go to those responsible for producing operational news and

01:09:47 say this is far too narrow this does not cover the recommendation made to the odcb

01:09:53 back in march 2015 or in june 2015 i'm not sure if peter cow had that conversation with gary reason

01:09:59 or anyone else i wasn't aware of that let's go to the final page of this operational news issue

01:10:04 please page eight you can see a list of the training associated with each of the articles

01:10:11 and if we look at the third row down it says fires in highly insulated buildings

01:10:16 and we have two uh by now familiar policies seven nine three compartment firefighting

01:10:22 article policy and then there's a training package high rise firefighting pn 633 and then highly

01:10:28 insulated buildings computer-based training package cbt and that's on big learning now peter groves

01:10:34 told us that that cbt package like the others was developed and signed off but not released because

01:10:39 of it issues namely the difficulty with local stations being able to play videos embedded within

01:10:46 the training packages and i'm summarizing his evidence but he that was what he said at day 177

01:10:52 page 74 to to uh page 181 there's quite a lot of it um do you agree with that yes i do you do do

01:11:00 you know why it was therefore that the operational news article referred to a cbt package that didn't

01:11:06 exist um i um i believe at the time that assurances were being given that uh that

01:11:14 it would be able to be used on fire stations right why was there no indication in this article that

01:11:19 the cbt package had been delayed but was forthcoming i'm not sure right peter groves also told us that

01:11:26 he remember discussing with the commissioning department which was your department as he said

01:11:31 the possibility of disseminating this training package without the videos but that was rejected

01:11:36 by your department on the basis that the video components helped to take the individual through

01:11:41 learning and if they didn't get that then there could be just as much of a risk as not doing

01:11:45 something rather a lot of the mouthful of this evidence but do you agree with that

01:11:49 no the we weren't the commissioning department we were the ones who'd taken the article to ops

01:11:53 news but because it was a firefighting policy and a firefighting piece of training that belonged to

01:11:59 peter cow up i know that graham ellis would have been very keen on ensuring the full training package

01:12:06 was available in order to articulate the point that he'd made previously that crews were unaware

01:12:12 of what some of these materials looked like and a package without the video and therefore the picture

01:12:18 evidence would have been a lower quality training and wouldn't have demonstrated those components

01:12:25 to the crews

01:12:40 do you accept that it would have been beneficial for crews to have received this package at least

01:12:45 in some form so that they were aware of the dangers and risks of impending sudden fire growth

01:12:51 and fire spread beyond the compartment of origin posed by modern materials and methods of construction

01:12:57 not least given the unprecedented increase in their usage across london yes it would have been

01:13:01 yes and what was it in the videos that was so fundamental that meant that the packages

01:13:06 couldn't be released without them i'm not sure i wasn't involved in the development of the training

01:13:11 package but mr chen and i've got one or two more questions on this before we come to the t cap

01:13:17 i can just i wouldn't finish them can i just yes um peter groves also told us that the lfb had

01:13:22 solved the problem for other training packages by sending the videos to stations on a cd or other

01:13:27 medium but that wasn't suggested for this package or there could have been do you know why that

01:13:32 wasn't considered why that workaround wasn't considered for these packages uh no that would

01:13:37 have been for peter groves to suggest as an idea as the um the interface with babcock's training

01:13:43 that would have been useful if we've been able to do that do you accept that while any of those

01:13:47 methods may not have been optimal they're not have been the best thing they would it would at

01:13:51 least have meant that crews would have had some kind of training which your department at least

01:13:55 knew to be risk critical yes that would have been and instead by the time of the granville tower

01:13:59 fire nearly two years later that training had simply not been rolled out to crews at all

01:14:05 yes that's uh it would have been better for them to have that information i agree

01:14:10 mr chairman is that convenient yes thank you very much we'll have a break now we'll come back please

01:14:16 at 25 to 4 and again please don't talk to anyone about your evidence or anything related to it

01:14:22 over the break thank you sir all right thank you very much thank you very much 25 to 4 please

01:14:39 you

01:15:09 you

01:15:39 you

01:16:09 you

01:16:39 you

01:17:09 you

01:17:39 you

01:18:09 you

01:18:39 you

01:19:09 you

01:19:39 you

01:20:09 you

01:20:39 you

01:21:09 you

01:21:39 you

01:22:09 you

01:22:39 you

01:23:09 you

01:23:39 you

01:24:09 you

01:24:39 you

01:25:09 you

01:25:39 you

01:26:09 you

01:26:39 you

01:27:09 you

01:27:39 you

01:28:09 you

01:28:39 you

01:29:09 you

01:29:39 you

01:30:09 you

01:30:39 you

01:31:09 you

01:31:39 you

01:32:09 you

01:32:21 would you ask miss cotton to come back in please

01:32:33 all right scott and ready to carry on yes sir thank you yes yes yes mr chairman the t cap

01:32:39 is cotton lfb 0010 2213

01:32:48 this is t cap 0 212 which we can see from the first page is entitled ops news 30 highly insulated

01:32:56 buildings and if we go to page three we can see that in the version control grid version 0.1 was

01:33:04 created on the 14th of october 2015 by nick markwell agreed draft for submission to babcock and

01:33:13 version 0.2 which is which is this was created on the 10th of october 2019 also by nick markwell

01:33:21 final draft for closed down c explanation in section 11.1 now taking it slowly can we go please to page

01:33:28 four box 1.2 name of commissioning officer and their department dac graham ellis operational

01:33:37 assurance now dac wayne brown so at the time of the initiation in october 2015 it's right that it was

01:33:43 graham ellis wasn't it um i think it was assigned graham ellis because of the ops news article

01:33:48 and then obviously subsequently passed to dac wayne brown do you know when no i have no idea

01:33:55 but at all at all events do you agree with me that the commissioning officer

01:33:59 was dac graham ellis of your department yes because the ops news article was related to him

01:34:06 but the content of the training would fall under peter cow up because of the fact that he owned

01:34:14 all of the policies in relation to firefighting policies and therefore subsequently any training

01:34:22 material that would fall from those and the name of the client and their department is dave brown

01:34:29 director of operations now andy row director of operations that would be in 2019 yes that's

01:34:35 correct at the bottom of page four you can see there's background and context you'll need to

01:34:41 scroll down it says this the key thrust of the ops news article 30 and package is that fs should be

01:34:47 aware of the implication on their firefighting tactics of the increasing use of highly insulated

01:34:53 sealed compartments fire development in these compartments and the hazards associated with

01:34:57 modern methods of construction the article and package should highlight a number of key concerns

01:35:02 and developments relating to modern methods of construction and signpost the new stroke improved

01:35:07 more than modern methods of construction cbt package the emphasis in the cbt package should

01:35:12 be on the implications modern methods of construction for firefighting tactics this should be in greater

01:35:17 depth than currently exist in the training package it is not sufficient to talk about rapid

01:35:23 fire spread and or unusual fire spread through voids straight cavities etc now mr groves told

01:35:31 us that that text there would have been provided by nick markwell in consultation with your

01:35:36 department as the commissioning department do you agree i think it would probably have been in

01:35:42 conjunction with tom goodall from operational policy who was listed further up who was in

01:35:48 charge of the firefighting section of operational policy i expect that graham ellis would have

01:35:55 worked in conjunction with them and i also saw lee drawbridge listed in there as well so

01:36:00 i think that would have been as it were a combined effort of those people right now you've picked on

01:36:06 something that i didn't show you so i'm assuming that your familiarity with that is from your

01:36:10 preparation but let's go back to page four to pick up what it is that you've seen this is under

01:36:15 paragraph 1.4 t cap stakeholder group members and we see tom goodall and lead rawbridge identified

01:36:23 there yes yes that's right i'm just like to say i have never seen this document i read that as you

01:36:28 put that up on the screen before i read those two names oh i see okay well that was very fast but

01:36:33 anyway there they are tom goodall and lead rawbridge lead rawbridge ops assurance yes yes that's

01:36:39 correct so also your department yes as part of the stakeholder group that would have been important

01:36:43 yes uh what makes you so sure that the text of the background and context that i've just read to you

01:36:53 at the foot of page four was provided not by nick markwell in consultation with your department

01:37:00 but in consultation with tom goodall no sorry to reiterate i think it was probably a combination of

01:37:05 but tom goodall was the group manager in charge of all of the firefighting policies for operational

01:37:11 procedures and this would therefore sit within him but i am pretty sure that lead drawbridge

01:37:16 would have provided assistance as well thank you now let's move ahead to uh well before we do that

01:37:21 the final sentence there if we can just have that back on the screen sorry we've lost it but page

01:37:25 five last sentence there it is not sufficient that spelled out didn't it that the current training

01:37:31 packages were not sufficiently addressing that topic i would say so yes i say this is the first

01:37:36 time i've seen this uh t cap yes now let's move ahead to page seven see see how far we get with

01:37:41 it box 4.1 what do you want this training to achieve and your department wrote the following

01:37:47 or rather it was written the following cbt package has referenced the following

01:37:52 first bullet point background for the development of increasingly well sealed compartments

01:37:55 global drivers for reduced co2 emissions and energy composite conservation conservation etc

01:38:01 technologies that are used to make this happen celtx which i think should be celotex king span

01:38:07 etc triple glazing aluminium ceiling tapes passive house rating building specific fixed

01:38:13 installations and other technological solutions this sort of technology is being retrofitted

01:38:19 in old buildings under development so not just found in new builds this sort of technology is

01:38:24 highly interdependent if one aspect fails it can undermine the entire design solution

01:38:31 signpost the bre research and the no g guidance as a resource both for operational staff but also

01:38:37 writers of training and policy and then this specific firefighting strategies to address the

01:38:44 hazards associated with high compartment fuel loading and temperature associated with modern

01:38:49 building contents we get less compartment fires but when they happen they are hotter and more

01:38:54 vigorous and they can be different to an old victorian semi that might traditionally have been

01:38:58 our bread and butter what a perfect response should look like consideration of ventilation path

01:39:04 weight of attack pro jet covering jets cruise external safety officer monitoring and communicating

01:39:11 window straight compartment failure and effects crews can anticipate on the compartment fire

01:39:16 conditions now looking a little bit more closely at the third from last bullet point in that list

01:39:23 signpost the bre research and the no g guidance as a resource for both for operational staff but

01:39:29 also writers of training and policy do you recall what that bre research and no g guidance was

01:39:37 no as i say i'm not familiar with this document so i'm i'm not familiar with the

01:39:41 research they're talking about and and which national operational guidance that would have been

01:39:48 group manager tom goodall as he worked in the operational policy where the guidance would have

01:39:53 been translated into london fargo policy right um you didn't see this t cap at the time as we can

01:39:59 see yet it was commissioned by graham ellis um i think as i said i explained i think initially his

01:40:05 name was put on it because the ops news article neither graham ellis nor lee drawbridge wrote the

01:40:10 content of this um i can tell by the style and by some of the phrases used which is not something

01:40:16 either of those officers would have put in the expression traditionally would have been our

01:40:20 bread and butter would not be a sentence that either of those two would use whose sentence was

01:40:25 it i have no idea but it's not the style and um type of context that either of those two would

01:40:33 use in a report right well on the footing then that this is a document you didn't see at the time

01:40:40 and had apparently no input into um let's see how you go the the bre research and no g guidance you

01:40:48 can't help us with can i show you a document and see if you could help with it lfb triple zero two four one seven four

01:41:01 this is something called the bre national operational guidance program fires in the

01:41:07 built environment knowledge and information and it's a very long document it runs to some 191 pages

01:41:13 uh have you ever seen this before no i haven't you've never seen this before no i haven't right

01:41:20 well you may come back to it in due course but again perhaps shortly do you know if this guidance

01:41:27 even though you haven't seen it before was shared with firefighters and writers of training and

01:41:30 policy i have no idea no idea um let's get back to the t cap form then please at page seven

01:41:36 lfb double zero one zero two two one three page seven at the foot of the page paragraphs two

01:41:44 four point two and four point three

01:41:48 lfb double zero one zero two two one three

01:41:57 uh

01:42:03 we can see from the foot of the page at four point two and four point three uh who do we need to train

01:42:08 four point two firefighters watch managers watch officer led cbt package station managers group

01:42:14 managers self-study package four point three when do we need this training cbt package to be delivered

01:42:20 in december 2015 you can see that and that would coincide wouldn't it with the release of operational

01:42:27 news 30 in january 2016 yes it would that was the idea why was that training limited to levels

01:42:33 one and two incident commanders as we see i have no idea sorry i wasn't party to this right would

01:42:40 you have expected this self-study package to be provided to all senior staff of all levels

01:42:47 i would expect it to be accessible on the brigades intranet for any officers to study yes yes now the

01:42:54 t caps progression was in fact discussed at the odcb do you remember that uh no i don't recall

01:43:00 that let's go to lfb triple zero four zero seven one one this is the odcb meeting for the 31st of

01:43:07 march 2016 and we can see that you were in attendance there as the second named attendee

01:43:14 down in the list and that was after your promotion to director of safety and assurance on the 1st of

01:43:19 december 2015 wasn't it yes it was if we go to page two you can see in there that under item 4a

01:43:27 there is an item dynamic and intelligent operational training and procedures update and that if you look

01:43:33 at roman numeral three it says this fire in highly insulated buildings is a computer cbt package

01:43:40 which has been developed but not gone live yet due to it issues it was confirmed that the it solution

01:43:45 lays with the lfb and it was hoped that these issues would be resolved with the it rollout

01:43:49 that is expected to begin in may and you can see from the right hand column that the action there

01:43:56 is assigned to dos and a see that i do yes uh that was you wasn't it yes but i think just to be clear

01:44:07 there are a number of actions uh detailed there um and so some of those would have been specific

01:44:13 to individual people so that what they should have done was to put the names against each of the roman

01:44:20 bullet points to say who that was assigned to well uh all right um it looks as if and this is the way

01:44:29 i read it but this is wrong that that assignation sorry the allocation uh to those um three or four

01:44:38 individuals for officers dosa hota and um br stroke dmo stroke hfs apply to all of those

01:44:51 um i'm not sure that it did but um we would have all had some responsibility in um i was we were

01:44:57 aware about the issues around the it and those were then being escalated to the head of it

01:45:04 um who worked for sue budden because uh it was taking an extraordinary long time to attempt to

01:45:11 resolve this issue and we kept being promised that the solution was imminent right um just for our

01:45:18 assistance which of these roman numerals what uh were allocated to you for action and i couldn't

01:45:25 tell from him i can see uh the roman numeral four actually has uh um my name there at the bottom

01:45:33 but the others i couldn't be specific it was not a terribly clever way of uh allocating actions on

01:45:39 the grounds of the fact that it'd be better if it'd been specific but i know that i definitely um

01:45:44 had a conversation with um sue budden who in which the department the it department sat

01:45:51 about my frustration on the issues right um now as one of the three directors by this time what

01:45:57 steps did you take to rectify the problem uh by speaking directly to sue budden who was the

01:46:03 director in which the it department sat right now this is of course march 2016 given the

01:46:08 significant impact on training packages can you tell us why the it issues which had originally

01:46:13 been identified in 2014 were not treated as a priority or handled with more expedition

01:46:19 they were treated as a priority but um unfortunately i'm not familiar with it

01:46:25 um

01:46:33 to be produced that was as much as i could do because i'm so i'm not familiar with it

01:46:38 and just by pressing the issue with the director responsible was my role at that time can you help

01:46:45 with this question that these it issues were insurmountable or non-insurmountable

01:46:51 i'm sorry i don't understand let me try it there was a bad question do you accept that these it

01:46:55 issues were not insurmountable they could have been surmounted if we'd had an it fix yes absolutely

01:47:00 yes and they're not withstanding that these basic it issues denied crews important training

01:47:05 yes they did now let's look at the contents of the highly insulated buildings package

01:47:11 uh can we go first to the watch based package which is a b.a.b. six zeros one six

01:47:17 um this is dated the 21st of may 2019 so this is almost two years after the granville tower fire

01:47:25 itself but you i think uh were still commissioner at this stage yes i was yes yes and we can see

01:47:33 the packages aims and objectives at page three if we go to that

01:47:36 uh and you can see a slide and underneath the slide text aim and objective standard information

01:47:42 aim to increase awareness of highly insulated compartments and associated operational

01:47:47 considerations objectives describe how highly insulated compartments impact on firefighting

01:47:53 techniques and strategies and how they impact on fire safety and safety and safety and safety

01:48:01 insulated compartments impact on firefighting techniques and strategies

01:48:06 and then summarize how this technology may fail and the related hazards explain the risks of

01:48:11 increased fire loading in relation to modern building contents outline what best practice

01:48:16 should look like at an incident with a highly insulated compartment list the technology and

01:48:22 building techniques used in construction to reduce co2 emissions and improve energy conservation

01:48:28 but that's what the aim was if we go to page seven we can see as part of a series of slides

01:48:34 on modern methods of construction a slide on thermal insulation boards

01:48:41 uh and that has a an image above it uh and the text says increasingly used in construction

01:48:51 as a core panel system for internal structures and into external cladding often the boards are

01:48:57 constructed of polyurethane pur or polyisocyanurate pir and are covered with an aluminium foil facing

01:49:05 modern methods of construction to create environmentally efficient buildings

01:49:09 a range of specialized building materials have been developed that's what it says uh the only

01:49:17 video we've been able to identify in this package appears to be associated with a series of slides

01:49:22 which start at page 15 and if we go through pages 15 16 17 and 18 can we do that you can see 15

01:49:31 modern day fire development 16

01:49:38 fire loading 17 fire loading 2 18

01:49:47 fire loading 3 and just looking at that would you agree that that is demonstrating that the cbt

01:49:52 package is playing a video of the difference in the time it takes to reach flash over as between

01:49:59 modern rooms on the one hand and older or legacy rooms on the other uh yes it appears to i'm not

01:50:05 familiar with this uh do you agree that that video is was not essential to disseminating

01:50:12 to disseminating information about modern construction methods and insulation materials

01:50:17 and the risks they pose um if that's the only video then yes i agree yes and actually even

01:50:23 the contents of the video could have been easily explained by a text or even still images yes they

01:50:29 could have been so do you agree that the decision not to release this package without its inessential

01:50:33 video content lacked any proper justification um if that was the original video that was embedded

01:50:39 or whether this has been updated and a different video embedded i i wasn't aware of the content so

01:50:45 if that was the only video then yes now we hold a copy of the training guide which accompanies this

01:50:50 watch based package at bab 6038 can we please can we please go to that

01:51:01 and it's called training guide highly insulated buildings e-learning watch manager led and if

01:51:06 you look at the bottom of the screen you can see um it's a doc ref babcock lesson template

01:51:15 and the authors of jonathan blow and divina latang do you know them no i've never heard of them

01:51:25 if we go to page 20 we can see the text

01:51:27 next

01:51:32 unseen fire spread read the following text to the watch the effectiveness of compartmentation

01:51:39 relies on good workmanship at installation and it being in a good state of repair failure to seal

01:51:45 gaps and voids reduces the fire stopping element of construction and can contribute to the unseen

01:51:50 spread of smoke stroke fire from one compartment to another the increased use of thermal insulation

01:51:56 boards can add to these problems as they are seen as less as a less effective fire barrier

01:52:00 than traditional materials the material they are constructed from can degrade and release

01:52:06 flammable and toxic gas the insulation properties of the material may make it difficult to track

01:52:12 fire spread uh the senior officer packages at bab 709 i don't propose to to take you to it because

01:52:21 it has similar contact content and only contains the the video i've shown you already just looking

01:52:27 at that do you agree that this training was essential for crews to understand the risks

01:52:32 facing them in the modern built environment yes as part of a training package definitely and do

01:52:38 you accept that in not releasing it or otherwise disseminating its contents down to station-based

01:52:43 staff at the very least that was a significant failure by the operational assurance department

01:52:48 um no because the operational assurance department weren't responsible at that time for releasing

01:52:52 this training i agree that not sharing that training with operational crews was um a risk

01:52:59 to crews because we weren't keeping informed about these modern methods of construction

01:53:04 do you accept that in not releasing this package that was a very significant failure uh by somebody

01:53:11 it was a significant failure yes by whom i'm not sure at this time who was responsible for

01:53:16 releasing the training package i'm sorry well we know where the t cap assigned its origins your

01:53:24 department and also tom goodell and lee drawbridge lee broad drawbridge being within your department

01:53:30 and that was um back in uh 2015 uh and 2016 what changed between the two years between then and

01:53:41 2019 um so dr sabrina cohen hatton was in charge of the operational review team the

01:53:48 instant command team i also believe peter critchell was in charge so there were a

01:53:52 number of different offices in charge of that team and also in charge of the operational policy team

01:53:57 and probably the teams working in peter grove so that's why i find it hard to identify

01:54:02 which individuals had been responsible during that time in those posts right well let's get

01:54:08 back in time then i've shown you the package that was eventually rolled out in 2019 let's get back

01:54:13 in time to 2016 and the 31st of march 2016 lfb 00088900 this is the same date as the odcb meeting

01:54:27 this is the training package document and it's set it's called dynamic and intelligent operational

01:54:32 training update says diot babcock 31st march 2016 do you remember uh this diot report being

01:54:40 circulated at the meeting not specifically no but it but you can remember you can't disagree

01:54:47 that it would have been i suppose no if it's on the minutes and this agenda yes it would have been

01:54:51 if we look at paragraph 1.1 of the report uh it says this report identifies how training interventions

01:54:58 have been reviewed and amended in line with the requirements of operational news 30

01:55:03 any amendments to training interventions have been subject to the training commissioning and

01:55:07 alterations process t cap the updates that were necessitated by operational news on fires in

01:55:14 highly insulated buildings we can find set out at set out at page four let's just go to page four

01:55:20 now on page four you can see that changes were identified for a b and c

01:55:37 firefighter development the importance of recognizing different types of buildings and

01:55:41 the hazards associated with these is reinforced through ffd training this subject is also supported

01:55:46 by e-learning packages and training notes building construction and firefighting in buildings you see

01:55:51 that i do yes and then if you go down to the third paragraph on this page incident command

01:55:59 incident scenarios are being created for the rollout of the new ic training across levels one to

01:56:03 three the injects for a range of these scenarios will include hazards and signs associated with

01:56:09 highly insulated buildings the content of the article will be raised by trainers during the

01:56:13 delivery of current incident command training we've seen no evidence to indicate that the

01:56:19 lessons underlying the highly insulated buildings package were worked into the new incident command

01:56:23 training packages or or that injects were developed specifically dealing with those issues

01:56:30 do you know whether they were uh no i'm not sure i've not um seen the full suite of incident

01:56:36 command training packages and the detail behind them to be able to confirm that do you know what

01:56:42 work was done on this uh no i'm unaware this would have been work that babcox would have been

01:56:48 undertaking to include that in the training they were developing right do you remember you may

01:56:54 not but when watch manager dowden who was the initial incident commander at granfell gave

01:57:00 evidence at part one of the inquiry he said that he didn't recall receiving training on looking out

01:57:04 for early unexpected failure of internal compartmentation or the impact of building

01:57:10 materials and contents on fire spread that was day nine at pages 41 and 42 for those who want

01:57:17 to get back to their transcripts in the light of his evidence do you accept that the new incident

01:57:23 command courses did not adequately incorporate or replicate the content of the highly insulated

01:57:29 buildings training package i can't confirm that because that would have assumed that

01:57:36 mike dowden had been subject to that training package and i wasn't aware if he had

01:57:40 as i said i haven't i haven't seen the content of those so i would be able to confirm or deny that

01:57:45 i'm sorry i don't know the detail of them right can i then turn to the national operational guidance

01:57:54 on fires in the built environment which is a similar topic do you remember that in 2014 while

01:57:59 you were ac operational assurance the national operational guidance program published a document

01:58:05 called fires in the built environment not specifically no right lfb 000 24174

01:58:16 we looked at this a moment ago and i said i'd come back to it and i think you didn't recall it

01:58:20 um it's that document there um now uh this document consists of some knowledge sheets

01:58:29 and i just want to see how much of this you can help us with can we go to page 25

01:58:36 this is on the subject of cladding you see i do yeah external wall finish cladding uh now

01:58:43 before i go into the detail you say this is a document you've never seen before are you able

01:58:48 to explain why that given that this is a 2014 document you as head of operational assurance

01:58:57 didn't see this document um it wasn't commonplace for um the national operational guidance documents

01:59:07 to be um read by everybody because this was used to translate into training

01:59:14 and policy for london fire brigade so the national operational guidance was issued

01:59:18 and there was a department which sat within peace cowops department that translated national

01:59:24 operational guidance into london fire brigade policy which would then be disseminated why was

01:59:29 that not of interest to the operational assurance department i'm not saying it wasn't of interest

01:59:33 i'm saying that that was the way the policy works so we wouldn't necessarily have had the

01:59:37 national operational guidance shared with us yes i'm just trying to understand why this document

01:59:42 would have bypassed you was it not your department's concern to make sure that key health and safety

01:59:49 risks uh whether to firefighters or to members of the public which were incorporated in national

01:59:56 operational guidance was seen by your department no because these would have been seen by the

02:00:01 operational policy department who wrote london fire brigade's operational policy that would then

02:00:05 translate into the workings of london fire brigade and how that was disseminated to firefighters to

02:00:11 ensure that firefighters and members of public were made safe right just miss cotton just remind

02:00:17 me what did your department do so operational assurance was responsible for monitoring performance

02:00:22 of operational activities on the fire ground and through the use of the operational review team

02:00:29 to feedback on those and also to provide information via the diop process to odcb to allow

02:00:36 operational news articles to be developed yes yes um operational activities on the fire ground so

02:00:43 in a nutshell say that we're clear because of some of the evidence we've heard today i just

02:00:46 want to be crystal clear about what your job was uh as a coa was to make sure that operations on

02:00:54 the fire ground were up were reasonably adequate if i could put it that way yeah better than that i

02:01:00 would hope all right better than that did that not mean that you would have to know and understand

02:01:07 what training people on the fire ground were getting in order for them to be able to perform

02:01:12 in accordance with the better than adequate standards you expected of them so the role of

02:01:17 the operational review team would be to review the performance of firefighters and officers on

02:01:21 the fire ground against london fire brigade policy so very much the policies that have been

02:01:26 developed by london fire brigade they would be aware of those and they would monitor the

02:01:30 performance of the crews against those are you saying that national operational guidance was

02:01:37 irrelevant to your job unless and until it was incorporated effectively domesticated into london

02:01:43 fire brigade policy it wasn't irrelevant but london fire brigade the operational assurance team

02:01:50 would work to london fire brigade policies which were developed from national operational guidance

02:01:54 by the operational policy team so that in making assessments assuring to use the word of the title

02:02:02 of your department the performance of those on the incident ground at any incident you are not

02:02:07 concerned to look at national standards only lfb's policy and training nothing else now i was fully

02:02:13 aware that the operational policy team were the ones who were reviewing the national guidance and

02:02:17 then incorporating that into london fire brigade policy which is what we trained london firefighters

02:02:23 to and therefore we would assess them against and your role when it came to training was to

02:02:28 make sure that the training fitted with what you understood to be the role of the firefighter on

02:02:35 the fire ground no we had no role in assuring the training that was done by peter groves team

02:02:42 and the training department and independent assurance and then the training on fire stations

02:02:46 that took place was assured by dave brown's training officers the trios and then the triple

02:02:53 sos who were subsequent team that went and monitored their training i didn't ask you about

02:02:57 whether you had a role in assuring the training what i'm really seeking to understand is what your

02:03:02 role was in relation to training at all we didn't have a role in relation to training and yet you

02:03:07 were the commissioning department in so many of the t caps that we've seen in only the ones relating

02:03:11 to instant command well and in relation to the to this package which i said was because of the

02:03:19 initially to do with the operation news 30 and it was then transferred to the operational policy

02:03:23 department who were the owners of the policy and therefore were developing the training

02:03:29 let's look at page 25 a little bit in a little bit more detailed then description external

02:03:34 cladding is commonly a non-structural material or assembly that is used to cover structural surfaces

02:03:40 on the outside of the building for aesthetic reasons insulation or to provide protection

02:03:43 from weather and climate and then under the heading general considerations in the box below

02:03:50 there's a list of cladding materials set out prefaced by the sentence cladding may be combustible

02:03:56 or non-combustible depending on the material used the following materials are typically used to

02:04:02 provide external cladding applied to the face of the building envelopes and then there's a list of

02:04:07 starting with clay then we have concrete thin stone metal steel which says steel stainless

02:04:14 steel copper bronze and aluminium are generally used in sheet form for cladding to walls as

02:04:19 profiled metal sheeting metal panelling aluminium and steel profiled cladding

02:04:26 and then you can see from the rest of the bullet points below that how that material

02:04:30 and insulation would be installed in the system and what the installation material might consist of

02:04:36 and then if you turn the page

02:04:43 it says cladding systems may also require an insulation material which is typically fixed to

02:04:48 the supporting structure using a combination of mechanical fixings both plastics and steel

02:04:53 adhesives and in some cases railing systems on uneven surfaces for general refurbishment

02:04:58 or masonry based systems a single product is typically applied to the supporting structure

02:05:03 using a combination of mechanical and or adhesive based systems on uneven or lightweight frame

02:05:08 systems that require a cavity between the insulation layer and the sheathing boards

02:05:13 railing systems are typically applied insulation insulating materials typically used in external

02:05:19 cladding systems fall into the following groups and then you can see non-combustible as the first

02:05:25 thermo setting as the second and that refers to polyurethane foam pur poly iso cyanurate

02:05:32 foam pir and phenolic foam and you can see that then it goes on at the end these products are

02:05:39 often faced with materials such as glass fiber or aluminium foil and then finally

02:05:47 it goes on to say after that list in the paragraph if we scroll down a little bit below

02:05:55 the the bullet points as follows the fire performance of minor items such as breather

02:06:00 membrane brains vapor barriers and gaskets also needs to be considered in isolation they may not

02:06:05 pose a fire risk but when used over large surface areas in multi-story dwellings they have the

02:06:11 potential to contribute to fire spread on or through the system by offering a route to bypass

02:06:17 fire prevention measures such as fire breaks and cavity closers and then if you go to page 27 you

02:06:24 can see that there are two types of two types of rain screen cladding system there ventilated

02:06:32 and unventilated but if you look at the bottom of that on the right hand side under inherent hazards

02:06:41 if we scroll down it says the potential for external fire spread with combustible cladding

02:06:46 systems hidden fire spread behind cladding this can lead to a second seat of fire if the fire

02:06:51 spreads upper cavity and breaks out higher up the structure falling debris may present a hazard to

02:06:58 people outside of the building or cause downward fire spread and if you look a little bit above

02:07:03 that you can see that in the context of a ventilated cladding system in the last paragraph

02:07:09 or pronouncement paragraph falling combustible cladding may cause fire spread to floors below

02:07:14 the original or primary seat of fire cladding which has plastic or aluminium components may

02:07:20 also produce molten droplets when exposed to fire which may drip onto people or objects below

02:07:26 the failure of cladding may leave the underlying structure of the building exposed this may aid

02:07:30 firefighters in the identification of the structural elements and materials used within the building

02:07:35 but may also leave the structure more exposed to the fire now that's an awful lot there

02:07:43 uh and is that something um that as of 14 was well known within the lfb and when i say that i mean

02:07:55 everything i've just read to you um no unfortunately i don't think it was why is that um i'm i don't know

02:08:02 that would have been a document that i said their operational policy team would have referred to

02:08:09 in the development of their policy um i was not aware but clearly in the national operational

02:08:13 guidance the number of areas are highlighted there that i don't think were translated into

02:08:19 either training or information that was given to firefighters yes and do you accept that as of 2014

02:08:27 there were materials available to fire and rescue services nationally including the

02:08:31 london fire brigade through the national operational guidance program that forewarned the lfb of what

02:08:37 cladding was and the fire risks that it posed um yes this document clearly states that yes and

02:08:43 that as head of operational assurance which encompassed the brigades health and safety

02:08:48 department at the very least do you accept that your department should have been alive to alive

02:08:53 to and implementing that guidance um no unfortunately as i said that guidance and the translation of

02:08:58 that into policy sat within the operational policy department therefore we would not have

02:09:03 been involved in this even though related to health and safety yes that's correct

02:09:10 leaving aside whose fault within the lfb it was do you accept that in failing to issue any form

02:09:16 of policy or training that covered cladding the brigade was at fault in failing to follow and

02:09:21 implement national guidance yes i do and and a failure in its health and safety responsibilities

02:09:28 both towards crews and to members of the public yes i do looking at page 86 please at this

02:09:35 document this is a knowledge sheet on means of escape in buildings higher than 18 meters but

02:09:41 under 30 meters as you can see from the very top of the screen uh and uh it goes on to express

02:09:49 general considerations and below that it has inherent benefits and inherent hazards

02:09:54 uh under inherent benefits it says increased fire resistance additional provisions to assist

02:10:00 firefighters provisions should be in place to limit external fire spread from the building

02:10:05 and then the third element of inherent hazards says firefighters should be aware of facade failures

02:10:12 and the potential for exposed edges of the building at height again do you accept that this was

02:10:18 forewarning all fire and rescue services including the lfb of the need to prepare

02:10:24 firefighters for facade failures yes it is and the failure to do so was a failure adequately

02:10:30 to implement national guidance yes it was yes can i then turn to the question of international fires

02:10:38 uh can we start with lfb 3024114 please

02:10:51 this is an email if you look at the second email down from peter cow up to russ timpson

02:11:00 copied to a number of people including you date of the 22nd of february 2015

02:11:05 subject high-rise fire in dubai dear russ you will no doubt be aware of the above and i was

02:11:11 wondering whether through the good offices of the international tall building fire safety

02:11:15 network you could put me in touch with some relevant individuals who would have been involved

02:11:19 in and or might have firsthand knowledge of this incident although lfb has recently invested

02:11:25 significant effort to improve our high-rise firefighting techniques and procedures we are

02:11:31 never complacent and it is hard to imagine that an incident on this scale won't bring forward some

02:11:37 lessons learned quotes unquote my focus would be any quotes new unquote issues associated with

02:11:43 firefighting operations and in particular to identify whether this incident highlighted any

02:11:48 command procedural or tactical issues which are not already which are not already covered in

02:11:54 the

02:12:07 then if you skip to the bottom peter carp says in addition my colleague assistant commissioner

02:12:12 neil orbell will be interested in any prevention or protection issues arising from this incident

02:12:17 so i would be also i would also be grateful if you would you could bear this in mind when suggesting

02:12:22 any contacts which you are able to offer first what was the international tall building network

02:12:28 can you tell us i've not heard of it before do you know what came of this email

02:12:34 no i'm not aware i don't i'm not whether whether i saw any reply to it or not why was it sent to

02:12:39 you do you think um peter cow up had a habit of copying a lot of people in on his emails for

02:12:44 information um and i think it would have been for that purpose did your operational assurance

02:12:49 department take any steps to obtain further details of the incident um no because i think

02:12:53 uh as covered by their peter cow up um who obviously was the um holder of the policies

02:13:00 in relation to firefighting there was clearly chasing that information and also had usefully

02:13:05 copied neil orbell as the assistant commissioner for fire safety and because they would obviously

02:13:11 have a key interest in that as well so it was being covered by the two departments who would be

02:13:16 taking that up indeed but can we proceed on the basis that he thought it was relevant because

02:13:22 your department covered health and safety and therefore he thought it was something that you

02:13:26 should know about i think he thought we should know about it because it was a an incident of

02:13:31 interest yes yes and therefore as an incident of interest were you not interested oh absolutely and

02:13:39 but i could see quite clearly that the people who would take the relevant action to progress any of

02:13:45 those issues were the ones that were being highlighted in this email by peter cow up

02:13:49 including himself and neil orbell did you yourself give any consideration to whether there was any

02:13:55 learning or operational assurance to be gleaned from that incident uh no i know that if peter

02:13:59 cow up had found any he would have shared that with us right is it because it was international

02:14:06 that you didn't think there was much to learn no not at all i mean i think that um graham alice as

02:14:11 well was very interested in international fires so it wasn't the fact there would be nothing to

02:14:16 learn um it was the fact that i knew the right people were uh involved in this email to pick

02:14:22 up the information may you say graham alice was very interested in international fires

02:14:26 had your directorate or the operational assurance department under your leadership between march

02:14:32 2012 and december 2015 been made aware of any other international or indeed domestic cladding

02:14:38 or facade fires um i think that we've been made aware of other fires i can't recall the specific

02:14:43 details but um graham alice uh where he was aware of them would share information you don't recall

02:14:50 any uh not off the top of my head sorry let's go to lfb 000 24217 this is an email chain from january

02:15:00 2016 almost a year later and the subject matter of the email chain is do by fire

02:15:09 uh and if you go to the email at the foot of page one you can see it's from graham graham alice

02:15:19 to lee drawbridge martin freeman copy to you and tony byles do by fire yes yes but tony byles

02:15:29 uh he's a name we may come across at some later stage but he was a long serving um firefighter

02:15:36 wasn't he yes he was he was a senior officer in the national resilience team he was and in fact

02:15:42 am i right in saying that he was actually incident commander at uh the adair house fire i'm not sure

02:15:49 oh you're not sure all right um we will come back to him in due course um but looking at the email

02:15:56 it says fyi interesting article about flammable polyurethane and aluminium building cladding

02:16:03 involved in the do by fire and he provides a link to an article on a site called if sec global

02:16:09 you see that yes i can um we'll look at the article in a moment but just before we do can

02:16:15 we look at the middle email uh sent on the 7th of january 2016 at 1507 just above it

02:16:23 tony byles and tony byles there is a group manager national resilience as you've said

02:16:28 and he says always knew clause 12.7 would be used somewhere by someone

02:16:33 relied on it heavily throughout my career regards tb um what's that about um i think

02:16:40 unfortunately that's tony byles having a private joke about something i'm not sure what clause

02:16:46 12.7 is but um he was very good friends with graham ellis um it didn't detract in any way

02:16:53 for the fact we had a conversation actually around uh this fire because graham ellis was signed up the

02:16:58 if sec notifications um but i think that was just tony making a comment and then i made a comment in

02:17:05 response to that so it wasn't a relevant piece of information i have no idea what clause 12.7 is

02:17:09 that tony was referring to but it was just a flippant comment i believe well you you've

02:17:14 dropped a hill a little bit in the in the in the um process of question and answer um first of all

02:17:20 i think as you've just told us you didn't understand what he meant by clause point seven

02:17:24 why didn't you ask him because i i knew by the tone of that that he was um being flippant

02:17:30 being flippant about what i don't know but i knew he was being flippant i knew tony well he was

02:17:35 good friends with graham and i knew that he was being flippant about clause 12.7 whatever that

02:17:40 was so i knew he wasn't referring to it in a um context of something he worked on or relied on

02:17:46 heavily throughout his career but were you not curious to know what he meant he clearly thought

02:17:50 it was important no he didn't he was being flippant i think and i'm i know that from a

02:17:55 conversation i've had subsequently with graham ellis about it did you look at the article yes i did

02:18:01 you could have told them from the article that this was a enormous external external cladding fire

02:18:07 yes and therefore um flippancy may have been regarded perhaps as out of place but tony

02:18:13 bars was certainly getting at something serious wasn't he um so we did have a conversation

02:18:17 between graham ellis lee drawbridge um and other colleagues around this fire um as a result of that

02:18:25 um tony bars wouldn't have been there because he was actually seconded out of london fire brigade

02:18:29 at that time working for national resilience but the colleagues in operational assurance did

02:18:34 have a conversation following viewing that video yes i take it from what you said just a moment to

02:18:41 go about 12.7 uh that you didn't think at the time that that was a reference to approved document b

02:18:48 guidance paragraph 12.7 no i didn't uh did you know at the time that that was the very paragraph

02:18:54 which had the requirement for insulation products used in the external walls of buildings over 18

02:18:59 meters to be of limited combustibility no i didn't in the top email that you send back

02:19:06 the same day a few minutes later i'm surprised it's taken them so long to reference such a key

02:19:11 piece of information what do you mean by that it was a response to tony bar's flippant comment

02:19:17 well i know but what did you mean by it um it was just a response to that there meant nothing by it

02:19:21 but what was the key piece of information that you were referring to i'm not sure i have no

02:19:25 recollection of that was it adb 12.7 i don't know i have no idea looking at the email run

02:19:32 from someone who wasn't involved in it at the time that is a fair reading of it doesn't it

02:19:38 if you didn't understand the context and the people involved in it yes possibly but i know

02:19:42 it wasn't because i know that tony bars would not have been familiar with approved document b

02:19:49 from the roles he'd conducted in london fire brigade any more than i was because i'd never

02:19:54 been a fire safety officer right um well let's look at the article which may provide a clue

02:19:58 that is at inq 3014890 and the article is entitled fatalities will happen sooner or later warns fire

02:20:12 safety expert after dubai blaze resurrects fears over flammable cladding and there is a photograph

02:20:18 of the new year's eve fire at the dubai hotel there the torch and you can see that there is

02:20:28 quite a lot of text below the picture uh the fire and it says this um the fire that engulfed a 63

02:20:36 story dubai hotel on new year's eve is a harbinger of fatalities to come a leading fire safety expert

02:20:41 has warned the fire which rapidly engulfed the address hotel's exterior sorry the address not

02:20:47 the torch the address hotel's exterior shortly before midnight is the third such blazes in many

02:20:52 years resurrecting fears about the prevalence of highly combustible materials among skyscrapers

02:20:56 across the uae 16 people suffered minor injuries in the latest blaze although there were no

02:21:02 fatalities a fire safety consultant with gloss door based cwb fire safety has warned that there

02:21:07 will be fatalities sooner or later speaking to the daily telegraph phil barry estimated that up to

02:21:13 70 percent of dubai's high-rise buildings could be clad in polyurethane and aluminium composite

02:21:18 cladding a highly flammable material used routinely during dubai's building boom the material was only

02:21:24 outlawed in the emirate in 2013 the basic rule is that outside any building over 13 meters which is

02:21:31 as high as any fire truck ladder can reach must be made of non-combustible materials because you

02:21:36 cannot fight the fire he said large numbers of buildings in the uae do not meet that standard

02:21:41 and then if you look at the foot of the page if you look at the foot of the page you can see it

02:21:46 says tall british buildings have been required to comply with british safety standard bs 476

02:21:52 which meets the class nought standard stipulating no surface spread of flames

02:21:57 since regulations were changed in the aftermath of the 1973 summerland holiday park fire on the

02:22:03 isle of man on the isle of man which killed 50 people and injured eight seriously

02:22:09 um now um can we take it i've read you quite a lot of that but can we take it that your directorate

02:22:16 and you particularly uh were well aware of this fire yes we were did you give any consideration

02:22:23 at that point around a year following the previous email we looked at to directing the operational

02:22:29 assurance department to revisit the international fires perhaps graham ellis in particular given his

02:22:35 interest to investigate why these fires were occurring and whether there was anything for

02:22:39 the lfb to learn from them or be prepared or take from them for preparation purposes

02:22:45 i think i do recall a conversation i had with graham ellis and other colleagues other senior

02:22:52 officers in different departments and i think the thrust of the conversation was that we were very

02:22:57 glad that in the united kingdom we had building regulations and bridge safety standards that would

02:23:04 not allow products such as this to be applied to buildings um it was i remember watching the fire

02:23:10 as it happened and you know seeing how rapidly it spread um and then reading this it was you

02:23:16 know very worrying that 70 percent of dubai's high-rise buildings were covered in it but the

02:23:21 bit at the bottom was the bit that i believe that um you know everyone thought that british

02:23:28 buildings complied with the fact that there would be no surface spread of flames so whilst we could

02:23:34 see that was happening overseas i think the issue that we raised was the fact that we were very glad

02:23:38 that we had far better protection in the united kingdom to not allow building materials such as

02:23:44 that to be used on buildings did anybody take any steps within the lfb to obtain details of this

02:23:49 incident the address fire for example to see what materials had in fact been used and whether a

02:23:55 similar incident could occur in london um i'm not sure they did um whether the fire safety department

02:24:02 who would have been the ones um who related to building construction materials would have done

02:24:07 that i'm not sure but i'm not aware and if you look at the bottom of the page which i think you

02:24:19 you are interested in we can see the reference to british standard 476

02:24:24 but a little bit above it it identifies the fact that although there is a basic rule in the uae

02:24:31 for non-combustibility of buildings over 30 meters large numbers of buildings in the uae do not meet

02:24:36 that standard why was that different from the position in london and i ask that because

02:24:43 polyurethane and cladding were materials as we've seen identified in the highly insulated

02:24:48 building cbt package um because i believe as it says at the bottom that tall british buildings

02:24:54 were required to comply with the british safety standard that they were not in the uae

02:24:58 and therefore there should be no surface spread of flames on any building that complies with bs 476

02:25:06 clearly those standards didn't apply in dubai at the time of this article in email january 2016

02:25:13 so 18 months or so before the grandville tower fire was it the view or the attitude of the london

02:25:18 fire brigade that an incident such as the address fire in dubai simply couldn't happen in this

02:25:24 country because of our regulatory regime i think it was a view that was held nationally by the

02:25:32 british fire service that no fire like this should ever be able to happen because we had british

02:25:37 safety standards and building compliance that should prevent any of this happening yes

02:25:43 what about the risk of non-compliance the risk that the regulations in question may not have

02:25:47 been complied with in the case of any given building that was a risk i'm not sure if that

02:25:52 was a risk that was ever identified or brought to anyone's attention but clearly there is

02:25:57 always a risk of non-compliance but i don't think that we had seen example in sort of something of

02:26:03 this case where that had happened and if we had then it wasn't shared widely

02:26:11 mr chairman i'm in the middle of a line of examination but i'm not going to finish it

02:26:14 before 4 30 not least because we're beyond 4 30 you've probably got a little further to go

02:26:19 with this too haven't you a little bit yes i do well it's an uncomfortable place to leave this

02:26:24 hanging but unless you want to sit for another 10 or 15 minutes to finish it off i think we're

02:26:29 not in trouble with no not in the slightest not at all i would think that this cotton's probably

02:26:34 had a long enough day already and maybe others have as well so i'm sorry to break you at a

02:26:41 less than convenient point but i think we can come back to this and pick it up again tomorrow

02:26:46 yes is that right yes yes well um as you have this cotton this line of questioning hasn't

02:26:54 come to an end but i think it's better if we stop now and we'll resume at 10 o'clock tomorrow

02:27:00 please i think you'd already arranged to come to my venture yes i had something yes good thank

02:27:04 you well we'll resume at 10 o'clock tomorrow then please and as before please don't discuss your

02:27:08 evidence with anyone over the break all right thank you very much that's a good reason too

02:27:16 thank you for the drill

02:27:24 thank you for a minute well we'll continue at 10 o'clock tomorrow then please thank you very much